System Sensor Model D4120A — Specifications
-
Model No.: D4120A
-
Type: 4-Wire Photoelectric Low-Flow Duct Smoke Detector
-
Sensor: Photoelectric, with plug-in sensor head for improved false-alarm immunity
-
Air Velocity Rating: 100 ft/min to 4,000 ft/min (0.5 m/s to 20.32 m/s)
-
Operating Temperature Range: –4 °F to 158 °F (–20 °C to 70 °C)
-
Operating Humidity Range: 0% to 95% RH (non-condensing)
-
Mounting Configuration: Flexible; supports square or rectangular duct footprints
-
Sampling Tube Installation: Front or back installation—no tools required
- Enclosure Features:
- Increased wiring space and ¾″ conduit knockout
- High-contrast terminal labels for easy wiring
- Pivoting housing for flexible mounting
-
Testing: Easy-access Test/Reset button that works with cover in place; supports remote testing (RTS151KEY or RTS2-AOS)
-
Indications: Dual LED status indicators (Standby, Maintenance, Trouble, Alarm)
-
Interconnectivity: Up to 50 units can be interconnected; only the alarmed unit activates, isolating the source of smoke
-
Wiring Protection: Built-in short-circuit protection from operator wiring errors
-
Field Configuration: DIP-switch settings for cover tamper, number of sensors, and trouble shutdown
-
Relay Contacts: Two DPDT Form-C relays, rated for AC/DC control use
-
Power Input: 24 VAC/DC or 120 VAC
-
Backward Compatibility: Compatible with existing Innovair accessories and products